The short answer
A short AI text prompt uses about 0.3 watt-hours by most estimates, and Google measured 0.24 for its median Gemini prompt. U.S. data centers used about 192 terawatt-hours in 2024, 4.7% of U.S. electricity, and Lawrence Berkeley National Laboratory projects 649 terawatt-hours in 2030. Worldwide, the International Energy Agency counts 485 terawatt-hours in 2025, heading to about 950 in 2030.
- A short text prompt uses 0.24 to 0.31 watt-hours across Google, Epoch AI and Microsoft Research estimates. Long or reasoning outputs can use more than ten times as much.
- Per-prompt figures leave out training, and they differ in whether they count idle machines and cooling.
- U.S. data centers used about 192 TWh in 2024, 4.7% of U.S. electricity, according to Lawrence Berkeley National Laboratory.
- The Laboratory's reference case is 464 TWh in 2028 and 649 TWh in 2030, and data centers would drive about a third of load growth to 2030.
- Globally, the IEA counts 485 TWh in 2025, up 17%, and projects about 950 TWh in 2030.
- One gigawatt running for a year is 8.76 TWh, about as much as 810,000 to 840,000 average U.S. homes use.
How much electricity does one AI prompt use?
For a short text prompt, about 0.3 watt-hours. A watt-hour is the energy a one-watt device uses in an hour. The estimates come from different methods, and they agree more than they differ.
| Source | Figure | Method | What it leaves out |
|---|---|---|---|
| Google, median Gemini text prompt, May 2025 | 0.24 Wh | Measured on its production serving fleet, including idle machines and data center overhead | Training, outside networking and user devices. Self-reported and not independently verified |
| OpenAI's chief executive, June 2025 | 0.34 Wh for the average query | No method or boundary given | Not stated |
| Epoch AI, February 2025 | About 0.3 Wh for a typical GPT-4o query | Modeled from assumptions, including 500 output tokens | Training and image generation |
| Microsoft Research, revised June 2026 | Median 0.31 Wh, and 3.91 Wh when outputs are about 15 times longer | Bottom-up model for models over 200 billion parameters on H100 servers, using published throughput benchmarks and assumed power draw. Median 300 output tokens | Training, tool calling, multi-step agents and network latency |
| Mistral, July 2025 | No energy figure. 1.14 grams of carbon dioxide and 45 mL of water per 400-token reply | Lifecycle assessment, including server manufacturing | User devices |
Google's 0.24 watt-hours splits into 58% for the AI chips, 25% for host processors and memory, 10% for idle machines and 8% for data center overhead, with rounding. Counting only the active chips, in the busiest and most efficient 10% of data centers, would give 0.10. Google says that is closer to the narrower method used in earlier studies. Its active chips across the whole fleet use 0.14. Google also says the energy per prompt fell 33 times in the 12 months to May 2025, which is its own claim.
Two cautions apply. A longer output uses more energy, so the figure for a reasoning model or a long document is higher than for a short answer. And water figures are not comparable: Google's counts on-site cooling, and Mistral's is a lifecycle figure.
Why is the total large if each prompt is small?
Because of the number of prompts. At Google's 0.24 watt-hours, one gigawatt running for a year, which is 8.76 terawatt-hours, would cover about 36.5 trillion prompts, by Spezia's arithmetic. That ignores training, which none of these figures include.
Microsoft's researchers calculate that serving a billion queries a day needs about 0.7 gigawatt-hours a day, or about 1.7 if a tenth of the queries are long. That total is larger than the per-query medians because it adds a 31% allowance for uneven demand, spare machines and networking, and averages over a wide spread of query lengths. The same paper says widely cited estimates are overstated by four to twenty times.
How much electricity do U.S. data centers use?
Lawrence Berkeley National Laboratory publishes a widely used U.S. estimate. It is built from equipment shipments, power per device and cooling simulations, not from meters, and it leaves out cryptocurrency mining.
| Year | Electricity | Share of U.S. electricity | Basis |
|---|---|---|---|
| 2023 | 176 TWh | 4.4% | December 2024 report |
| 2024 | 192 TWh | 4.7% | June 2026 update |
| 2028 | 464 TWh | Not stated | June 2026 reference case |
| 2030 | 649 TWh | 11.8% | June 2026 reference case, with a range of 521 to 843 TWh |
The two reports use different data, so do not subtract one row from the other. On the June 2026 basis, 2023 was about 168 TWh, by Spezia's arithmetic, because the update reports 14% growth from 2023 to 2024.
The December 2024 report projected a range of 325 to 580 TWh in 2028, or 6.7% to 12.0% of U.S. electricity. The 2026 reference case for 2028 sits in the middle of that range. In power terms, the December 2024 report's range for 2028 corresponds to 74 to 132 gigawatts, at an assumed 50% utilization. The June 2026 update puts 2030 at 148 gigawatts on the same assumption.
The June 2026 update says data centers would be responsible for about a third of load growth from 2024 to 2030. It revised earlier years slightly down, mainly because fewer GPUs shipped in 2023 and 2024 than first reported. GPU-accelerated servers, the AI machines, grew from under 2 TWh in 2017 to more than 40 TWh in 2023, counting server electricity only.
And across the world?
The International Energy Agency counts 415 TWh for data centers in 2024, about 1.5% of global electricity, with 45% of it in the United States. Its 2026 update says demand grew 17% in 2025 to 485 TWh, and projects about 950 TWh in 2030, roughly 3% of global demand. It says AI-focused data centers grew 50% in 2025 and would triple over 2025 to 2030. A typical AI-focused data center uses as much electricity as 100,000 households, and the largest under construction use about 20 times that.
What does a gigawatt mean?
A gigawatt is a rate of power, and a gigawatt-year is an amount of energy. One gigawatt running flat out for a year is 8.76 TWh. Dividing by the Energy Information Administration's average household use gives about 810,000 to 840,000 homes, using 10,791 kilowatt-hours a year for 2022 and 865 a month for 2024.
Spezia's tracker, as of November 9, 2026, holds 294 U.S. projects that are not yet operating and report a capacity. Together they plan 285 GW. Some are only announced, and some are blocked or paused. If every one of them ran flat out for a year, it would use about 2,497 TWh, against about 4,200 TWh of electricity the United States consumed in 2025. That is an illustration of scale, not a forecast. Capacity here is planned full build-out, most projects will not be built on their stated schedule, and none run flat out. See the U.S. AI data center pipeline and the gigawatt power wall.
How do you read an AI energy headline?
Six checks help.
- Per prompt, per task or in total? A watt-hour, a training run and a national total are very different scales.
- What is inside the boundary? Chips only, whole servers, idle machines, cooling and training give different numbers.
- Average or median? A few long outputs can lift an average.
- Measured or modeled? Google measured its fleet. Epoch and Microsoft modeled.
- Power or energy? Gigawatts measure capacity. Terawatt-hours measure use over time.
- Which year? Efficiency changed quickly, so a 2023 figure may not describe 2026.
Open the power tracker for planned plants, capacity by state and the grid news that decides which data centers get built. Ask Spezia which projects are waiting on power.
See where the power for AI comes fromHow this was made
Per-prompt figures are read from each publisher's own paper or page, with what each counts and leaves out. National and global totals are read from Lawrence Berkeley National Laboratory, the International Energy Agency and the Energy Information Administration. Gigawatt conversions are Spezia's arithmetic and show their inputs. Planned capacity comes from Spezia's project tracker. Every estimate is labeled as measured, modeled or self-reported.
The data was read on November 10, 2026. Figures change as new research lands, and this post is updated when they do.
Sources
- Measuring the environmental impact of delivering AI at Google scale, Google, on arXiv
- The gentle singularity, Sam Altman
- How much energy does ChatGPT use?, Epoch AI
- Energy use of AI inference, efficiency pathways and test-time scaling, Microsoft Research, on arXiv
- Our contribution to a global environmental standard for AI, Mistral AI
- 2024 United States data center energy usage report, Lawrence Berkeley National Laboratory
- United States data center energy usage report: 2025 update, Lawrence Berkeley National Laboratory
- Energy and AI: energy demand from AI, International Energy Agency
- Key questions on energy and AI: executive summary, International Energy Agency
- Use of electricity, U.S. Energy Information Administration
- Frequently asked questions: electricity use in a home, U.S. Energy Information Administration
- Energy and AI: executive summary, International Energy Agency
- Residential electricity consumption and price in 2024, U.S. Energy Information Administration
- Measuring the environmental impact of AI inference, Google Cloud
- Spezia U.S. data center project tracker, Spezia
Common questions
How much electricity does a ChatGPT query use?
OpenAI's chief executive said about 0.34 watt-hours for the average query, without giving a method. Other estimates of a short text prompt, from Epoch AI and Microsoft Research, are near 0.3 watt-hours, and Google's own measurement is 0.24. Long or reasoning outputs can use more than ten times as much.
How much energy does a Google Gemini prompt use?
Google measured 0.24 watt-hours for the median Gemini text prompt in May 2025, counting idle machines and data center overhead. It excludes training, and Google says the figure is its own and has not been independently verified.
What share of U.S. electricity do data centers use?
About 4.7% in 2024, or 192 terawatt-hours, according to Lawrence Berkeley National Laboratory's June 2026 update. Its reference case projects 464 terawatt-hours in 2028 and 649 in 2030, about 11.8% of projected U.S. electricity.
How much electricity do data centers use worldwide?
The International Energy Agency counts 415 terawatt-hours in 2024 and 485 in 2025, up 17%. It projects about 950 terawatt-hours in 2030, roughly 3% of global electricity. The United States held about 45% of the 2024 total.
How many homes does one gigawatt power?
About 810,000 to 840,000 average U.S. homes, if it runs flat out for a year. One gigawatt for a year is 8.76 terawatt-hours, divided by the Energy Information Administration's average household use.
Is AI's electricity use going to keep growing?
Every projection read for this page grows. The IEA projects roughly a doubling from 2025 to 2030. Lawrence Berkeley National Laboratory's reference case for U.S. data centers is about 3.4 times its 2024 level by 2030. The size depends on how many chips ship, how efficient they are and how many projects get built.
Cite this
Spezia. "How much electricity does AI use? From one prompt to the whole U.S. grid" Spezia, November 10, 2026. https://spezia.ai/blog/how-much-electricity-does-ai-use
You may quote and share this analysis with a link to the post. Plain-text version · RSS